Turbomachinery Package Specification Taurus 70 Compressor Set and Mechanical Drive
Pilot air operated primary gas fuel shutoff valve
Pilot air operated secondary gas fuel shutoff valve
Pilot air operated gas vent valve
Electrically operated fuel control valve
Torch with shutoff valve and pressure regulators
Main fuel manifold
Fuel injectors
For SoLoNOx combustion, the fuel system also includes:
Fuel pilot control valve
Fuel pilot manifold
Inlet gas filter/coalescer loose shipped for field installation
Component Operation
The gas fuel pressure supplied to the turbine skid must meet minimum and maximum
pressure and flow requirements. If the gas fuel pressure is too high or too low, the control
system will prevent turbine operation. Pneumatically actuated primary and secondary gas
fuel shutoff valves are controlled using pilot air pressure. For each valve, pilot air
pressure is admitted to and exhausted from a pneumatic actuator through a solenoid
valve. Fail-safe operation ensures both valves will close in case pilot air pressure is lost.
The gas fuel control valve and, when applicable, the SoLoNOx fuel pilot control valve, are
powered by integrated DC motor-driven actuators. Integrated actuator electronics provide
precise closed-loop valve control based on position command inputs versus position
feedback outputs. Both valves are fast acting and provide fuel metering for light-off,
acceleration, full load, and load transient conditions. Fail-safe operation ensures both
valves will close in case the command signal or control power is lost. During the start
sequence prior to ignition, the control system will verify gas pressure and perform a gas
valve check to verify proper operation of all gas fuel valves.
Table 8. Fuel System Specifications
Gas Fuel System
Acceptable Gas Fuels See Note (a)
Natural Gas
Propane
Fuel Quality Refer to Solar’s Engineering Specification ES 9-98
Optional Fuel System Types
Conventional Combustion or SoLoNOx
Combustion
Compliance
National Association of Corrosion Engineers
(NACE) Compliant
Minimum/Maximum Gas Fuel Supply Pressure
1860 to 2760 kPag (270 to 400 psig), See Note (b)
Minimum Flow Rate
1950 kg/hr (4297 lbm/hr), See Note (b)
Minimum/Maximum Fuel Supply Temperature
-40° to 93°C (-40° to 200°F), See Note (c)
Primary Gas Fuel Shutoff Valve Pneumatically Actuated Spring-Closed Ball Valve
Secondary Gas Fuel Shutoff Valve Pneumatically Actuated Vane Type Valve
Gas Fuel Control Valve and SoLoNOx Fuel Pilot
Control Valve (If Applicable)
Actuator Valve
Actuator Voltage 120 VDC
Valve Discrete Signals 24 VDC
Valve Analog Signals 4 to 20 mA
© 2009 Solar Turbines Incorporated. All rights reserved. TPS70CSMD/309
27